SBG01 heat flux meter

SBG01 is a water cooled heat flux meter
SBG01 heat flux meter has rapidly become the sensor of choice for fire testing
Water cooled heat flux sensor

SBG01 is a water cooled sensor that measures heat flux. The ISO standards call this a heat flux meter. Introduced in 2008, SBG01 has rapidly become the sensor of choice for fire testing. SBG01 is mainly used to test reaction to fire and fire resistance. It is also used as a calibration reference standard for test equipment, for example in flammability and smoke chamber tests. SBG01 complies with the requirements of the most common ASTM and ISO standard test methods.

Specifications
Measurand
  • Irradiance in W/m² (in SI units)
  • heat flux
Measurement range
  • (5, 10, 20, 50, 100, 200) x 10³ W/m²
Would you like a personalised quote?

or contact us: info@huksefluxindia.com

Specifications

Measurand
  • Irradiance in W/m² (in SI units)
  • heat flux
Measurement range
  • (5, 10, 20, 50, 100, 200) x 10³ W/m²
Sensor technology
  • both Gardon and Schmidt-Boelter
Rated cooling water temperature range
  • 10 to +30 °C
Rated cooling water flow
  • > 10 l/h (0.003 l/s) preferably 30 l/h (0.01 l/s)
Rated measurement ranges
  • (5, 10, 20, 50, 100, 200) x 10³ W/m²
Response time (63 %) at different measurement ranges
  • :
5, 10 x 10³ W/m²
  • < 450 x 10⁻³ s
20, 50 x 10³ W/m²
  • < 250 x 10⁻³ s
100, 200 x 10³ W/m²
  • < 200 x 10⁻³ s
Limiting measurement range
  • 150 % of rated measurement range
Output signal
  • DC voltage
Output signal range
  • > 5 x 10⁻³ V at rated measurement range
Spectral range
  • 0 to 50 x 10⁻⁶ m
Full field of view angle
  • 180 °
Black coating emissivity
  • > 0.95
Calibration traceability
  • to ITS-90
Calibration laboratory
  • :
-management system certification
  • ISO 9001
-accreditation
  • not accredited
Calibration method
  • SBGC secondary calibration method according to ISO 14934-3
Standard cable length
  • 2 m (see options)
Order code standard version
  • SBG01/rated measurement range/cable length
Options
  • rated measurement range (5, 10, 20, 50, 100, 200) x 10³ W/m²
  • longer cable (specify total cable length in m)
  • high temperature cable rated temperature range to 400 °C (specify length in m)
  • type T or type K thermocouple connected to instrument body (specify –TCT or - TCK), wire exiting next to signal cable. Wire diameter 0.5 x 10⁻³ m
  • smooth cylindrical body without flange (specify – C)
  • threaded cylindrical body without flange (specify – T), thread 1-12 UNF
Manuals & Downloads

Description

SBG01 is a water cooled heat flux meter

There are 6 models of SBG01

SBG01 measures heat flux in the range of (5 to 200) x 10³ W/m². Equipped with a black absorber, heat flux sensors of this type are designed for measurement in an environment in which heat flux is dominated by radiation. Using an open detector, SBG01 is also sensitive to convective heat flux. This contribution is usually ignored. Application in environments with lower than 50 x 10³ W/m² irradiance levels or environments with significant heat transport by convection is possible but requires a careful evaluation of the measurement uncertainty. SBG01’s thermopile sensor generates an output voltage proportional to the incoming irradiance. The sensor is water-cooled. There are 6 models of SBG01; each with a different rated measurement range, calibration reference irradiance level, sensitivity and response time. Water cooling is usually supplied by tap water. There are several optional body designs. The standard body is equipped with a flange. Common options are a smooth cylinder body without a flange (model -C) and threaded body (model –T).  Also a thermocouple (type T or K) can be fitted upon request.

SBG01 heat flux meter has rapidly become the sensor of choice for fire testing

Advantages

SBG01 has a novel sensor design, which combines the benefits of foil technology of the traditional Gardon gauges with those of the thermopile technology of the traditional Schmidt-Boelter gauges. SBG01 has several advantages: 

  • robust and serviceable water tubes
  • scratch resistant absorber coating (slightly lowered surface)
  • safe storage with a practical protection cap

Suggested use

  • SBG01 has rapidly become the sensor of choice for fire testing. SBG01 is mainly used to test reaction to fire and fire resistance. It is also used as a calibration reference standard for test equipment for example in flammability and smoke chamber tests
SBG01 heat flux meter
SBG01 is a water cooled heat flux meter
  • robust and serviceable water tubes
  • scratch resistant absorber coating (slightly lowered surface)
  • safe storage with a practical protection cap
  • durable cable with strain relief, temperature resistant up to 200 °C
Would you like a personalised quote?